Know your Regs - FREE Guide

x

Member Home / Technical Support / Electricity (Safety) Regulations 2010 (ESR), AS/NZS 3000 FAQ’s

Electricity (Safety) Regulations 2010 (ESR), AS/NZS 3000 FAQ’s

Certificate of Verification (COV) – When and How?

Required under ESR 74 for any installation that has been disconnected or isolated from supply for more than 6 months.

  • Minimum testing is to Section 3 of AS/NZS 3019 (Visual inspection)
  • Optionally, the person certifying can apply Section 4 (limited testing) or Section 5 (full testing) if required to gain confidence in safety.
  • If using Sections 4 or 5, all listed tests in the section must be completed – cherry-picking invalidates the result.

Insurer Requirements:

  • Not mandated under ESRs, but some insurers request a COV for commercial or older residential properties.
  • They may dictate the section of AS/NZS 3019 to test to and often request it be “without qualification.”
    ⚠️ That means no limitations like “as far as could be seen visually.” All reasonable access points must be checked.

Myth: You do not need to be an Inspector.
ESR 74(1) only requires someone authorised to certify mains work.

AS/NZS 3000:2018 – Can We Use It?

Not currently cited in the ESRs – even though it’s listed as “current” by SNZ.
It is cited in NZ Building Code Clause C (since Nov 2023, mandatory from Nov 2024) to support interconnected smoke alarms.
However, ESRs still only cite AS/NZS 3000:2007 (Schedule 2).

Important: If you’re doing prescribed electrical work (PEW), you must follow the cited 2007 edition for compliance.

Exception: If doing building work where Clause C applies, the 2018 edition may be referenced – e.g. in smoke alarm installation.

‘Kitchen’ Isolation – What Needs a Local Switch?

Under Clause 4.7.1 of AS/NZS 3000:2007, only a hob (electric cooking appliance) requires local switching.

  • The requirement is for a switch, not necessarily an isolator.
  • It must be readily accessible, ideally within 2 m of the appliance, and without reaching over hot zones.
  • There is no minimum distance, but AS/NZS 3000:2018 proposes 150 mm – not enforceable until cited.

Other appliances (ovens, rangehoods, fridges) do not require a local switch unless manufacturer’s instructions say so.

Socket Near a Tap – Any Rules?

No prescribed exclusion zones around outdoor taps or kitchen-style ‘pasta taps’.

  • Section 6 of AS/NZS 3000 defines “prescribed zones” these are typically water containers (e.g. baths, basins, pools).
  • So a socket near a garden tap (without a basin), or a tap above a cooktop, is not prohibited.

However, Section 4.1 (external influences) still applies:

  • Avoid placing sockets directly under taps
  • Consider IP-rated fittings and mounting positions to reduce water ingress risk

Do I Calculate for Balanced or Unbalanced Load?

Unless dealing with:

  • 3-phase resistive heating
  • 3-phase motors

… assume it’s unbalanced.
The presence of a neutral conductor almost always implies an unbalanced load.
Balanced protective device sizing across phases does not mean the current is balanced.

Does an Outbuilding Need Inspection?

Yes – theearthing system, is considered a main earthing system and is high-risk PEW:

  • MEN connection
  • Main earthing conductor (MEC)
  • Earth electrode

These must be inspected (ESR 6A and ESR 70).

Other work in the outbuilding (e.g. final subcircuits) is not high-risk unless other factors (e.g. medical, hazardous, mains parallel) apply.

Type B RCDs for EV Chargers?

WorkSafe EV Charging Guidelines provide best practice (not mandated by ESRs):

  • Mode 2 & Mode 3 EV chargers require protection from DC leakage.
  • If the charger includes a DC protection device compliant with IEC 62955 (RDC-DD), a separate Type B is not required.
  • You must still provide Type A RCD protection at the switchboard.

Socket outlets intended for EV charging:
Always recommend a Type B RCD, even for Mode 2, to futureproof against user changes.

I’m Not an Inspector – Can I Issue the First EWOF?

Yes – But only if:

  • You did the original installation
  • You issued the COC, per ESR 78(1)(c)

Use Appendix C of AS/NZS 3001 and the EWRB checklist.
Stickers can be ordered through your EW portal (print portal).
If you’re new to it, consider peer-review from an Inspector.

Do I Need to Lower a Main Switch Above 2 m?

Not necessarily.

ESR 59(3)(b) allows replacement of fittings in “original condition.”
Switchboards are assemblies, not single fittings, so each item is assessed on its own.

Replacing an old switch with a new DIN-mount one serving the same purpose = acceptable as replacement

If relocating significantly (e.g. across the house), or upgrading capacity (e.g. 63 A to 100 A), this is not a ‘like-for-like’ replacement and must comply fully with AS/NZS 3000 – including height limits.

Extending a Mains Conductor – When is it OK?

Under ESR 6A, limited relocation or extension of a conductor to facilitate replacement of a fitting is allowed.

Extending to suit a new neutral bar layout or reconfiguring around a DIN rail = justified
Relocating the mains entry point, or lengthening for capacity upgrades = new installation, full compliance required.

High-risk PEW may still apply – refer to Schedule 1 and ESR 6A interpretation.

Can I Install an Earth Electrode Near LPG Bottles?

AS/NZS 3000:2007 allows non-ignition sources (like earth electrodes) inside hazardous zones under 4.18.2/3.
BUT: ESR Schedule 2 modifies these clauses:

Only items directly associated with the gas supply can be installed in the hazardous zones shown in Figures 4.10/4.11.

So: Don’t install an earth electrode within these zones.

Socket Distance from Infinity Water Heater?

No hazardous zone or exclusion zone is defined under ESRs or AS/NZS 3000.

However, Section 4 still applies:

  • Avoid areas with potential splash or high humidity
  • Consider mechanical protection or IP-rated accessories

Do I Need to Replace TRS or VIR Cable?

Not mandatory.
ESR 113 (grandfather clause) allows older wiring to remain if:

  • It was compliant when installed
  • It is still electrically safe
  • It remains compliant to at least its original standard

IR readings < 1 MΩ or brittle, degraded insulation?  It must be replaced.
No, you shouldn’t reuse old cable – even if it “looks fine.”

Can I Run Cable Along the Ground?

Technically yes, but not ideal.

Per Note 3 of Clause 3.11.2, it’s not considered an underground wiring system.
Other exclusions include cable in ventilated troughs or embedded in concrete.

Use Section 3 of 3000 – installation must be:

  • Mechanically protected
  • Rated for external influence
  • Safe from water, pests, foot/vehicle traffic

Ground-mounted cabling often fails this bar unless very well protected (e.g. in conduit with mechanical shielding).

Does Off-Grid Solar Require Inspection?

It depends.

  • Main parallel generation = always high-risk PEW
  • Solar PV = only high-risk PEW if it exceeds ELV thresholds

ESR Schedule 1 excludes extra-low voltage (ELV) systems from being PEW if:

  • Not in a hazardous or medical location
  • Operate below 50 V AC or 120 V ripple-free DC

So:

  • ≤120 V DC off-grid PV = not PEW, no inspection
  • 120 V DC = PEW, and if solar, then high-risk → requires inspection

MEN Links in Sub-Boards – Remove?

Not mandatory.

Prior to the 2010 ESRs, multiple MENs were acceptable.
If the installation predates 2010 and the MEN at the sub-board isn’t creating EFLI or bonding issues, it can stay.

Removing it could push fault loop resistance out of spec. Use judgement.

Do I Need a Qualification for Thermal Imaging?

No – thermal imaging is not PEW, and not cited in regulations.
Anyone can use a thermal camera, but

Removing a switchboard cover is PEW (maintenance).
So while thermography itself isn’t restricted, accessing live terminals is – must be done by a licensed person.

Insurers may require a Category 1 thermography certification – check their terms.

Can I Withhold a COC for Non-Payment?

No. ESR 10 requires a Certificate of Compliance to be issued after completing PEW.
Not issuing one:

  • Is a breach of the regulations (Level 2 offence)
  • Weakens your position in any payment dispute

Issue the COC, then pursue payment through normal channels (e.g. debt recovery).

Back to top