Know your Regs - FREE Guide
Certificate of Verification (COV) – When and How?
Required under ESR 74 for any installation that has been disconnected or isolated from supply for more than 6 months.
- Minimum testing is to Section 3 of AS/NZS 3019 (Visual inspection)
- Optionally, the person certifying can apply Section 4 (limited testing) or Section 5 (full testing) if required to gain confidence in safety.
- If using Sections 4 or 5, all listed tests in the section must be completed – cherry-picking invalidates the result.
Insurer Requirements:
- Not mandated under ESRs, but some insurers request a COV for commercial or older residential properties.
- They may dictate the section of AS/NZS 3019 to test to and often request it be “without qualification.”
⚠️ That means no limitations like “as far as could be seen visually.” All reasonable access points must be checked.
Myth: You do not need to be an Inspector.
ESR 74(1) only requires someone authorised to certify mains work.
AS/NZS 3000:2018 – Can We Use It?
Not currently cited in the ESRs – even though it’s listed as “current” by SNZ.
It is cited in NZ Building Code Clause C (since Nov 2023, mandatory from Nov 2024) to support interconnected smoke alarms.
However, ESRs still only cite AS/NZS 3000:2007 (Schedule 2).
Important: If you’re doing prescribed electrical work (PEW), you must follow the cited 2007 edition for compliance.
Exception: If doing building work where Clause C applies, the 2018 edition may be referenced – e.g. in smoke alarm installation.
‘Kitchen’ Isolation – What Needs a Local Switch?
Under Clause 4.7.1 of AS/NZS 3000:2007, only a hob (electric cooking appliance) requires local switching.
- The requirement is for a switch, not necessarily an isolator.
- It must be readily accessible, ideally within 2 m of the appliance, and without reaching over hot zones.
- There is no minimum distance, but AS/NZS 3000:2018 proposes 150 mm – not enforceable until cited.
Other appliances (ovens, rangehoods, fridges) do not require a local switch unless manufacturer’s instructions say so.
Socket Near a Tap – Any Rules?
No prescribed exclusion zones around outdoor taps or kitchen-style ‘pasta taps’.
- Section 6 of AS/NZS 3000 defines “prescribed zones” these are typically water containers (e.g. baths, basins, pools).
- So a socket near a garden tap (without a basin), or a tap above a cooktop, is not prohibited.
However, Section 4.1 (external influences) still applies:
- Avoid placing sockets directly under taps
- Consider IP-rated fittings and mounting positions to reduce water ingress risk
Do I Calculate for Balanced or Unbalanced Load?
Unless dealing with:
- 3-phase resistive heating
- 3-phase motors
… assume it’s unbalanced.
The presence of a neutral conductor almost always implies an unbalanced load.
Balanced protective device sizing across phases does not mean the current is balanced.
Does an Outbuilding Need Inspection?
Yes – theearthing system, is considered a main earthing system and is high-risk PEW:
- MEN connection
- Main earthing conductor (MEC)
- Earth electrode
These must be inspected (ESR 6A and ESR 70).
Other work in the outbuilding (e.g. final subcircuits) is not high-risk unless other factors (e.g. medical, hazardous, mains parallel) apply.
Type B RCDs for EV Chargers?
WorkSafe EV Charging Guidelines provide best practice (not mandated by ESRs):
- Mode 2 & Mode 3 EV chargers require protection from DC leakage.
- If the charger includes a DC protection device compliant with IEC 62955 (RDC-DD), a separate Type B is not required.
- You must still provide Type A RCD protection at the switchboard.
Socket outlets intended for EV charging:
Always recommend a Type B RCD, even for Mode 2, to futureproof against user changes.
I’m Not an Inspector – Can I Issue the First EWOF?
Yes – But only if:
- You did the original installation
- You issued the COC, per ESR 78(1)(c)
Use Appendix C of AS/NZS 3001 and the EWRB checklist.
Stickers can be ordered through your EW portal (print portal).
If you’re new to it, consider peer-review from an Inspector.
Do I Need to Lower a Main Switch Above 2 m?
Not necessarily.
ESR 59(3)(b) allows replacement of fittings in “original condition.”
Switchboards are assemblies, not single fittings, so each item is assessed on its own.
Replacing an old switch with a new DIN-mount one serving the same purpose = acceptable as replacement
If relocating significantly (e.g. across the house), or upgrading capacity (e.g. 63 A to 100 A), this is not a ‘like-for-like’ replacement and must comply fully with AS/NZS 3000 – including height limits.
Extending a Mains Conductor – When is it OK?
Under ESR 6A, limited relocation or extension of a conductor to facilitate replacement of a fitting is allowed.
Extending to suit a new neutral bar layout or reconfiguring around a DIN rail = justified
Relocating the mains entry point, or lengthening for capacity upgrades = new installation, full compliance required.
High-risk PEW may still apply – refer to Schedule 1 and ESR 6A interpretation.
Can I Install an Earth Electrode Near LPG Bottles?
AS/NZS 3000:2007 allows non-ignition sources (like earth electrodes) inside hazardous zones under 4.18.2/3.
BUT: ESR Schedule 2 modifies these clauses:
Only items directly associated with the gas supply can be installed in the hazardous zones shown in Figures 4.10/4.11.
So: Don’t install an earth electrode within these zones.
Socket Distance from Infinity Water Heater?
No hazardous zone or exclusion zone is defined under ESRs or AS/NZS 3000.
However, Section 4 still applies:
- Avoid areas with potential splash or high humidity
- Consider mechanical protection or IP-rated accessories
Do I Need to Replace TRS or VIR Cable?
Not mandatory.
ESR 113 (grandfather clause) allows older wiring to remain if:
- It was compliant when installed
- It is still electrically safe
- It remains compliant to at least its original standard
IR readings < 1 MΩ or brittle, degraded insulation? It must be replaced.
No, you shouldn’t reuse old cable – even if it “looks fine.”
Can I Run Cable Along the Ground?
Technically yes, but not ideal.
Per Note 3 of Clause 3.11.2, it’s not considered an underground wiring system.
Other exclusions include cable in ventilated troughs or embedded in concrete.
Use Section 3 of 3000 – installation must be:
- Mechanically protected
- Rated for external influence
- Safe from water, pests, foot/vehicle traffic
Ground-mounted cabling often fails this bar unless very well protected (e.g. in conduit with mechanical shielding).
Does Off-Grid Solar Require Inspection?
It depends.
- Main parallel generation = always high-risk PEW
- Solar PV = only high-risk PEW if it exceeds ELV thresholds
ESR Schedule 1 excludes extra-low voltage (ELV) systems from being PEW if:
- Not in a hazardous or medical location
- Operate below 50 V AC or 120 V ripple-free DC
So:
- ≤120 V DC off-grid PV = not PEW, no inspection
- 120 V DC = PEW, and if solar, then high-risk → requires inspection
MEN Links in Sub-Boards – Remove?
Not mandatory.
Prior to the 2010 ESRs, multiple MENs were acceptable.
If the installation predates 2010 and the MEN at the sub-board isn’t creating EFLI or bonding issues, it can stay.
Removing it could push fault loop resistance out of spec. Use judgement.
Do I Need a Qualification for Thermal Imaging?
No – thermal imaging is not PEW, and not cited in regulations.
Anyone can use a thermal camera, but…
Removing a switchboard cover is PEW (maintenance).
So while thermography itself isn’t restricted, accessing live terminals is – must be done by a licensed person.
Insurers may require a Category 1 thermography certification – check their terms.
Can I Withhold a COC for Non-Payment?
No. ESR 10 requires a Certificate of Compliance to be issued after completing PEW.
Not issuing one:
- Is a breach of the regulations (Level 2 offence)
- Weakens your position in any payment dispute
Issue the COC, then pursue payment through normal channels (e.g. debt recovery).
Available Technical Support resources
- Repair guidance information for flood affected switchboards
- Emergency & Natural Disaster – Information & Support
- RCD Testing
- Phase Rotation Testing
- Insulation Resistance Testing
- Earth Fault-Loop Impedance Testing
- Earth Continuity Testing
- Correct Circuit Connections Testing
- Circuit Polarity Testing
- Electricity (Safety) Regulations 2010 (ESR), AS/NZS 3000 FAQ’s
- PEW classes
- SDoCs and manufacturer instructions for electrical equipment
- Access to Standards and Legislation